AP1001 HART Differential Pressure Transmitter
The AP1001 differential pressure transmitter is used to measure the differential pressure of different pressure points of liquid or gas, and then convert it into a 4-20mADC output, with the HART communication protocol.
Performance Specification
Accuracy of Range:
±0.1%(Including nonlinearity, hysteresis and repeatability)
Ambient Temperature Influence
The total amount of influence from -25℃ to 65 ℃ is:
±(0.15×TD+0.1)%×Span
The total influences at -40 ℃ to -25 ℃ and 65 ℃ to 85 ℃ are:
±(0.2×TD+0.1)%×Span
TD=maximum range/adjustment range
Over range Influence
±0.075%×Span
Stability
±0.1%×Span/year
Power Supply Influence
±0.001% /10V(14~45V DC), (it can be almost ignored)
Span and Range
Span Code |
Span kPa |
Range kPa |
B |
1~6 |
-6~6 |
C |
4~40 |
-40~40 |
D |
25~250 |
-100~250 |
F |
250~3000 |
-100~3000 |
Add :5/F,Building 1, No.1258, Ping'an Road, Minhang District, Shanghai,P.R.China